FIRE PUMP SELECTION
 All NFPA 20 fire pumps must operate with a flooded
suction condition.
 Fire pumps must not operate with a Suction Lift.
 Centrifugal pump for fire protection shall be selected to
operate at less than or equal to 150 percent of the rated
capacity
 Recommends operation between 90 to 140%
 Jockey Fire Water Pump is mandatory for Fire Water
pump system
 Jockey pump shall have discharge pressure sufficient to
maintain the desired fire protection system pressure.
WATER SUPPLY & MATERIAL
 Water supply shall be adequate, dependable and
acceptable to the authority having jurisdiction
 The acceptance of a well as a water supply source
shall be dependent upon satisfactory develop